| Feature | With test report | Without test report |
|---|---|---|
| CODE | QIT20-2 | QIT20-2-ST |
| Power | 20 kWp | |
| Three-phase inverter | 2 | |
| Main switch-disconnector (main circuit) | 4×63A | |
| Shunt trip coil (remote tripping control) | 230VAC | |
| Fuse switch-disconnector 1P+N (auxiliary circuit protection) | 10A fuse | |
| Fuse switch-disconnector 3P+N (interface relay voltage presence protection) | 10A fuse | |
| Fuse switch-disconnector 3P+N (surge protection circuit) | 32A fuses | |
| Three-phase surge arrester | Class II Imax 20kA | |
| Contactor 4P (interface device) | 40A – AC3 | |
| Interface relay | Compliant with CEI-021 | |
| RCBO (inverter protection) | No.2 4×20A 6kA – 300mA Class A | |
| Terminal block for cable input/output | Numbered | |
| Protection degree | Polyester – IP66 Class II | |
| Declaration of conformity | CEI EN 61439-1/2 | |
| Panel dimensions | 510 × 720 × 250 mm (W × H × D) | |