Electrical Panel Interface 50 kWp (2 inverters)

Feature Including bench test report Without test report
CODE QIT50-2 QIT50-2-ST
Power 50 kW
Three-phase inverters 2
Main switch-disconnector
(main panel switch)
4x100A
Shunt trip coil
(closing command)
230VAC
Fuse switch-disconnector 1P+N
(auxiliary circuit)
Fuse 10A
Fuse switch-disconnector 3P+N
(interface relay voltage presence)
Fuse 10A
Fuse switch-disconnector 3P+N
(surge arrester protection)
Fuses 32A
Three-phase surge arrester Class II – Imax 20kA
4P contactor (interface device) 95A – AC3
Interface relay Compliant with CEI-021
RCBOs (magnetothermal circuit breakers with RCDs)
(inverter protection)
No. 2 4x50A 6kA – 300mA Class A
Input/output terminal block Numbered
Protection degree Polyester – IP66 Class II
Declaration of conformity CEI EN 61439-1/2
Panel dimensions 610 × 820 × 300 mm (W × H × D)
Do you need more informations?

Call +39 080 967 5815 o or send us an email to info@secsun.it