Electrical Panel Interface 70 kWp (2 inverters)

Feature Including bench test report Without test report
CODE QIT70-2 QIT70-2-ST
Power 70 kW
Three-phase inverters 2
Main switch-disconnector
(main panel switch)
4x125A
Shunt trip coil
(closing command)
230V
Fuse switch-disconnector 1P+N
(auxiliary circuit)
Fuse 10A
Fuse switch-disconnector 3P+N
(interface relay voltage presence)
Fuse 10A
Fuse switch-disconnector 3P+N
(surge arrester protection)
Fuses 32A
Three-phase surge arrester Class II – Imax 20kA
4P contactor (interface device) 115A – AC3
Interface relay Compliant with CEI-021
RCBOs (magnetothermal circuit breakers with RCDs)
(inverter protection)
No. 2 4x63A 6kA – 300mA Class A
Input/output terminal block Numbered
Protection degree IP65 Class II
Declaration of conformity CEI EN 61439-1/2
Panel dimensions
Do you need more informations?

Call +39 080 967 5815 o or send us an email to info@secsun.it