Electrical Panel Interface 100 kWp (2 inverters)

Feature QIT100-2
Including test report
QIT100-2-ST
Without test report
Power 100 kW
Three-phase inverters 2
Main switch-disconnector
(main panel switch)
4x250A
Shunt trip coil
(closing command)
230 VAC
Fuse switch-disconnector 1P+N
(auxiliary circuit protection)
Fuse 10A
Fuse switch-disconnector 3P+N
(interface relay voltage presence protection)
Fuse 10A
Fuse switch-disconnector 3P+N
(surge arrester protection)
Fuses 32A
Three-phase surge arrester Class II – Imax 20kA
4P contactor (interface device) 175A – AC3
Interface relay Compliant with CEI-021
MCBs with residual current protection
(inverter protection)
No. 2 4x100A – 16kA adjustable
Input/output terminal block Numbered
Protection degree Metal enclosure – IP65 Class I
Declaration of conformity CEI EN 61439-1/2
Panel dimensions 955 × 1095 × 230 mm (W × H × D)
Do you need more informations?

Call +39 080 967 5815 o or send us an email to info@secsun.it