| Feature | Including bench test report | Without test report |
|---|---|---|
| CODE | QIT30-1 | QIT30-1-ST |
| Power | 30 kW | |
| Three-phase inverter | 1 | |
| Main switch-disconnector (main panel switch) | 4×63A | |
| Shunt trip coil (remote release control) | 230V | |
| Fuse switch-disconnector 1P+N (auxiliary circuit) | 10A fuse | |
| Fuse switch-disconnector 3P+N (interface relay voltage presence) | 10A fuse | |
| Fuse switch-disconnector 3P+N (surge arrester) | 32A fuses | |
| Three-phase surge arrester | Class II Imax 20kA | |
| 4P contactor (interface protection device) | 50A – AC3 | |
| Interface relay | Compliant with CEI-021 | |
| RCBO (residual current circuit breaker) for inverter protection | 1 pc. 4×50A 6kA – 300mA Class A | |
| Input/output terminal block | Numbered | |
| Protection degree | Polyester – IP66 Class II | |
| Declaration of conformity | CEI EN 61439-1/2 | |
| Panel dimensions | 400 × 610 × 257 mm (W × H × D) | |
Call +39 080 967 5815 o or send us an email to info@secsun.it